Foreword
Compact and Lightweight design that is ideal for moving from job site to job site or within your facility.
It offers the most robust, high-capacity designs in the industry. It is setting the standard with intelligent operator controls, safety indication layouts, adjustable load step resolution, and lightweight designs. It is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems.
Testing System

Note: Power cable and PC is not available. Picture just for reference, subject to the real products.
Supply List
The following form presents the accessories provided when we make shipment.
|
Items |
Quantity |
Remark |
|
KL100(100KW) Portable Load Bank |
1 |
|
|
RS485 Line |
1 |
10 meters |
|
RS232, RS485, USB converter |
1 |
|
|
Product Instruction |
1 |
|
|
Certification |
1 |
|
|
Warranty Card |
1 |
1 year |
|
Packing List |
1 |
|
|
Receiving Apron |
1 |
|
|
Data processing software |
1 |
|
|
Test Report |
1 |
Technical Parameter
|
KL(KW) Portable Load Bank |
|
|
Rating Voltage/Frequency |
400VAC 3 phase 4 wire, 50HZ/60HZ |
|
Rated Power |
Resistive load: 100kW |
|
Load Step |
Total 8 load steps: 1kW,2kW,2kW,5kW,10kW,20kW,20kW,40kW,. Could change from 1kW to kW freely, step value is 1kW. |
|
PF(Power Factor) |
1 |
|
Load Tolerance |
±3% |
|
Display Precision |
0.5 class |
|
Control Power |
External 230V single phase 50Hz |
|
Wire Connection |
Load power supply input--Copper bar (star coupling "Y") Control power supply input--3core power plug |
|
Communication Interface |
RS485 |
|
Insulation |
F |
|
Duty cycle |
Continuous |
|
Cooling |
Forced air cooling, horizontal air inlet & outlet |
|
Transportation |
Hoisting, there are lifting lugs on top |
|
Color |
Aluminum alloy white |
|
Dimension |
About 748*517*728mm |
|
Weight |
About 75kgs |
|
Operating Environment Parameter |
|
|
Workplace |
Indoor |
|
Ambient Temperature |
-20℃~+50℃ |
|
Relative Humidity |
≤95% |
|
Altitude |
≤2500 meter |
|
Atmospheric Pressure |
86~106kPa |
|
Brands of Main Components |
|
|
Contactor |
Schneider |
|
PLC |
Siemens |
|
Data processing software |
KINGWAY |
|
Resistor |
KINGWAY |
Function
1)User could load any power within rated power, can test stable state three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time of generating set.
2)Whether load/unload by local control panel or by PC software control, user can pre-set the power then press the master load button.
3)Control mode: user can choose local control or intelligent control(PC control)
4)Local manual control: there is local control panel in load bank, with multi load steps, min load steps 1kW, controlled by buttons.
5)Automatic control: user can control load bank by data processing software of PC to make automatic load/unload, display, record and manage the test data, form curve, graph and can be printed.
6)Control mode interlock: there is switch in control panel to choose control mode, other control mode is invalid if user choose one control mode.
7)With data processing software, could form curve of current, active power, reactive power, apparent power, power factor, frequency and can be printed.
8)One-key load/unload: user can load or unload with one key easy to control.
9)3 line LED multi-function meter display.
Data Processing Software Functions
1)Communication type: through, RS485 or USB interface.
2)Load mode: manual load or automatic load.
3)Manual load: input power and power factor.
4)Automatic load: User can set several periods of power and time, and in turn of 0%→25%→50%→75%→100% or 110%, etc
5)or other preset order (33%→66%→99%) to make automatic load testing.
6)Parallel testing: when several load banks parallel working, parameters of each load bank can be displayed and recorded, so do the final parameters of paralleling working.
7)Real-time parameter: Current, voltage, power, power factor, frequency, time, etc could be displayed by software.
8)Safety monitoring: User can know the working conditions of load bank through software indicating light. When in abnormal stop protection, software will indicate the reasons of stopping.
9)Data collection interval: the min saving interval is 2 seconds.
10)Data saving and in query: testing data could be saved in software, user can query at any time.
11) Data display: it could display real-time data and history data; user can print voltage, current, frequency, power graphs and charts.
12) Charts and graphs are output in format of JPG while testing data output in Excel format, and all can be printed.
Protection
1) User can press the emergency stop button in the panel to unload immediately when the load bank is abnormal while working.
2) Fan interlock protection: Load bank could not loading testing before start the fan.
Picture Show